How to Select Drop-Out Fuses Correctly?|Weicite Power Tech's Expert Guide
Cost-Effective 11kV Fuse Cutout, Rural Grids, 10-Year Warranty
Selecting the right High Voltage Drop-out Fuse is critical for transformer protection. Shandong Weichite Power Technology Co., Ltd. reveals key steps based on IEC/ANSI standards:
1. Voltage & Current Matching: Non-Negotiable!
Rated Voltage: Fuse voltage rating MUST match transformer system voltage (e.g., 11kV, 33kV).
Fuse Link Sizing: Apply the 1.5~2x Rule:
✅ Fuse Base Rating ≥ Fuse Link Rating
✅ Fuse Link Current = (1.5~2) × Transformer Full Load Current
Example: 100kVA 11kV transformer (FLA=5.25A) → Select 8-10A fuse link
2.Short-Circuit Capacity Verification
Validate interrupting capacity using:
System 3-Phase Fault Current < Fuse Breaking Capacity Upper Limit
Warning: Exceeding the limit risks catastrophic failure! For industrial users, Weicite recommends fuses with ≥16kA breaking capacity.
3. Model Selection: Beyond Basic Specs
Dynamic Tripping Curve**: Withstand transformer inrush current (20-25× FLA for 0.1s)
Environment Adaptation**: -40℃ versions available with silicone seals
Corrosion Resistance**: C5-M coating for coastal/chemical plants
Why Choose Weichite?
▶ Smart Selector Tool: Get model recommendations (e.g., Type-HV-12/100) in 30s
▶ Full-Range Solutions: From pole-mounted transformers (50kVA) to substations (2.5MVA)
▶ Global Compliance: KEMA-tested fuse links meeting IEC 60282-1
Case Study: A steel plant avoided $50k downtime by upgrading to 20kA fuses after fault current analysis.